Online
UPS TTX Series |
Technical
Specifications |
Model |
TTX10 |
TTX15 |
TTX20 |
TTX30 |
TTX40 |
TTX60 |
TTX80 |
TTX100 |
TTX120 |
Capacity |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
100KVA |
120KVA |
Power |
8KW |
12KW |
16KW |
24KW |
32KW |
48KW |
64KW |
80KW |
96KW |
Power Factor |
0.8 |
Input |
Phase |
3
phase 4 wire and ground |
Voltage Range |
+/-20% |
Frequency Range |
45
– 65Hz |
Rectifier |
3
phase 6 pulses |
Output |
Phase |
3
phase 4 wire and ground |
Wave form |
Sine
wave |
Crest Factor |
3:01 |
Rated voltage |
380/400/415V
optional |
Phase voltage setting |
200
- 244VAC (control panel ) |
Transient response |
+/-5%,
10ms |
Frequency |
50
/ 60 Hz |
Frequency stability |
+
/ - 0.05% |
Range of phase lock |
With
synchronization: +/-0.05% |
Without synchronization: + /- 2% (settable +/-1%
on the control panel) |
Total harmonic distortion |
3%
( linear load) |
Short circuit current |
Short
current for 0.1s (200% current) |
Overload capacity |
110%
/125% /150% rated current 300 min/ 10min /1min |
Battery |
Battery |
Maintenance
free lead-acid cell |
DC Voltage |
384VDC |
Bypass |
Type |
Static
state + manual maintenance bypass |
Input Phase |
3
phase 4 wire and ground |
Input voltage range |
15%
- 25% (the front control panel selectable) |
Input frequency range |
+/-1% ~ +/-
5% the front control panel selectable |
Transfer time |
Inverter
/ bypass transfer swiTTXh time(Overload): 0ms
inverter / bypass transfer swiTTXh time (fault inverter) 1ms |
Overload capacity (10 min) |
170% |
180% |
170% |
170% |
170% |
140% |
130% |
125% |
125% |
Remote signaling |
Dry
contact (battery low, battery discharging, bypass/ fault); output 12Vdc/80mA |
Remote control |
EPO
and bypass |
Communication interface |
RS232
( SNMP , modem optional ) |
Running temperature |
0-40
degree Celsius |
Relative Humidity |
Less
than 95% (without condensing) |
Altitude |
1000m
output nominal power (with increase of 100m, it will reduce output of
1%) max 4000m |
Noise at 1 M |
less
than 60 dB |
Inverter Efficiency |
92% |
|
Degree of protection |
IP20 |
Applicable Standards |
EN50091-1-EMC EN50091-2liv.A |
Optional |
Isolating
transformer |
Harmonic wave suppression filter |
Parallel modules can be up to six |
Net weight (Kg) |
210 |
230 |
230 |
282 |
330 |
450 |
555 |
650 |
750 |
Gross weight (Kg) |
260 |
280 |
280 |
332 |
380 |
505 |
600 |
700 |
800 |
Packing (W×D×H) |
650×850×1340 |
950×890×1620 |
1070×740×1400 |
|
|
|
|
|
|
|
|
|
|
|