High Frequency EXHFI | ||||
Technical Specification | ||||
MODEL |
EXHFI 500 | EXHFI 1000 | EXHFI 2000 | |
CAPACITY | VA/W | 500VA / 300W | 1000VA / 600W | 2000VA / 1200W |
INPUT | Phase | Single | ||
Voltage | 110 / 120VAC or 220 / 230 / 240VAC | |||
Voltage Range | 90 - 145VAC or 170-280VAC ( Narrow Range ) | |||
50-145VAC / 90-280VAC (Wide Range) | ||||
OUTPUT | Phase | Single | ||
Voltage | 120VAC or 230VAC | |||
Voltage Regulation(Batt. Mode) | +10% ~ 18% | |||
Frequency | 50Hz or 60Hz | |||
Frequency Regulation (Batt. Mode) | +/- 0.1 Hz | |||
Output Waveform (Batt. Mode) | Modified Sine Wave | |||
POWER FACTOR | P.F. | 0.6 | ||
BATTERY | Charger Current | 8 Amp + / - 1Amp | 6 Amp + / - 1Amp | 10 Amp + / - 1Amp |
Floating Voltage | 13.7V + / - 0.2V | 27.4V + / - 0.4V | 27.4V + / - 0.4V | |
Overcharge Protection | 15V +/- 0.3V charger stops and fault | 15V +/- 0.6V charger stops and fault | 30V +/- 0.6V charger stops and fault | |
TRANSFER TIME | Typical | 8ms | ||
EFFICIENCY | AC to AC | >95% | ||
DC to AC | >80% | |||
INDICATOR | AC Mode | Green LED lighting | ||
Battery Mode | Yellow LED lighting | |||
Battery Charging Mode | Green LED flashing every 2 seconds | |||
Overload | Red LED flashing every 0.5 second | |||
Fault | Red LED lighting | |||
AUDIBLE ALARM | Low Battery at Battery Mode | Sounding every 2 seconds | ||
Overload | Sounding every 0.5 second | |||
Fault | Continously sounding | |||
PROTECTION | Full Protection | Deep Discharge, Overcharge, and Overload protection | ||
PHYSICAL | Dimension (D x W x H) mm | 224 X 255 X 80 | ||
Net Weight (kgs) | 1.7 | 1.9 | 2.5 | |
ENVIRONMENT | Operating Environment | 0~40 Degrees Centigrade, 0~90% relative humidity (non-condensing) | ||
Noise Level | Less than 50dB | |||